PRODUCTS
-
LB6-110 Current Transformer
-
LB3-110 Current Transformer
-
LABN6-35 Current Transformer
-
JDCF-110 Voltage Transformer
-
TYD110 Capacitance Voltage Transformer
-
TYD35 Capacitance Voltage Transformer
-
JDN6-35/ JDXN6-35 Voltage Transformer
-
JDT-55 Voltage Transformer
-
GW4B-126 Outdoor High Voltage Disconnecting Switch
-
GW4-40.5 Outdoor High Voltage Disconnecting Switch
-
GW5-40.5/126(D) Outdoor High Voltage AC Disconnecting Switch
-
GW4-27.5 (D) Outdoor HV AC isolation switch
-
GN2-40.5 Indoor High Voltage AC Disconnecting Switch
-
GW8-40.5/72.5/126 Outdoor Neutral Point High Voltage AC Disconnecting Switch
-
GW13-40.5/72.5/126 neutral point outdoor high voltage AC disconnector
TYD35 Capacitance Voltage Transformer
Summary
Capacitance voltage transformer (CVT) is applied for voltage & electricity measuring and relay protection as well as carrier communication in outdoor neutral point earthing power system with 35kV rated voltage and 50Hz rated frequency.
TYD35 CVT composed of intermediate transformer, is directly led to electromagnetic unit by the medium voltage terminal of the capacity divider, compensation reactor and damper.
Capacity divider is composed of porcelain shell, capacitor core, capacitor oil and metal expander. The capacitor core, processed by vacuum dipping, is cascaded by several paper film compounds and components winded by aluminum foil. Within the porcelain shell are filled in capacitor oil and installed with metal expander to compensate the oil volume change as the temperature.
TYD35 CVT adopts rapidly saturated damper, featuring rapid instant response and reliable ferromagnetic resonance damping; secondary terminal box has carrier communication terminal and overvoltage protection gap; outside the oil tank are oil level meter, terminal box, rating plate, oil discharging stopper, earthing device. The product optimizes the sealing structure and has excellent sealing performance.
Working Environment
Ambient Temperature: Max. Atmospheric Temperature: +40℃; Min. Atmospheric Temperature: -30℃; Daily average atmospheric temperature: ≤+30℃ (able to provide special products)
Main Technical Parameters
| No | Name | Unit | Data |
| 1 | Rated Voltage | kV | 35 |
| 2 |
Rated Frequency |
Hz | 50 |
| 3 |
Phase Number |
Single Phase |
|
| 4 |
Rated Voltage of Primary Winding |
V | 35000/√3 |
| 5 |
Rated Voltage of Secondary Winding |
V | 100/√3 |
| 6 |
Rated Voltage of Reminding Windings |
V | 100/3 |
| 7 |
Rated Capacitance |
0.1μF/0.02μF | |
| 8 |
Load Limit of Reminding Windings |
3P/50VA | |
| 9 |
Accuracy |
0.2(or0.5)/3P | |
| 10 |
Rated Output |
VA | 50VA/50VA |
| 11 |
Total Weight |
kg | 420 |
Ordering Information
Please specify when ordering: Model Rated voltage, accuracy and other requirements
Dimensions

Related Products
Inquiry
Contact information
Rugao Yingrui High Voltage Electrical Equipment Co., Ltd.
If you have any suggestions or need for our products, please contact us!
CONTACT
Address:
No. 289, Fushou West Road, Rucheng Town, Rugao, Jiangsu
E-mail: